0x80EA

Expansion Rack Starting Word Address Exceeded

Omron · CJ-series CJ2 CPU Unit

¿Qué significa 0x80EA ?

An Expansion Rack's starting word address exceeds CIO 0901, preventing the CPU from correctly addressing the I/O for the rack. The corresponding bit in A409.00 to A409.03 (Racks 0 to 3) will be turned ON, indicating the affected rack.

Causas comunes

  • The first word setting for the Expansion Rack is configured above CIO 0900.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the first word setting for the Rack indicated by A409.00 to A409.03.

  2. 2

    Using a Programming Device (e.g., CX-Programmer), change the setting to a valid word address below CIO 0900.