0x80F0
Program Error
Omron · CJ-series CJ2 CPU Unit
¿Qué significa 0x80F0 ?
A general program error has occurred within the CJ2 CPU Unit, indicating incorrect program logic or an unrecoverable runtime issue. The program will stop, and the address at which the stop occurred will be output to A298 and A299. Specific sub-error flags (A295.xx) provide more detailed diagnostic information.
Causas comunes
- The PLC program contains logical or structural mistakes.
- A specific program sub-error has been triggered (e.g., No END, UM overflow, Task error, Illegal access, Indirect DM/EM BCD error, Instruction error, Illegal instruction).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check program error information using A298 and A299 to determine the program stop address.
- 2
Consult A295 error flags for specific sub-error details.
- 3
Correct the identified program mistake using a programming device.
- 4
Clear the error after correction.