Device Read Command Error (CIP)
Omron · CS/CJ Series EtherNet/IP Driver
¿Qué significa RHxx132 ?
An error response was received by the system when attempting a device read command from the external device via CIP. This indicates a problem retrieving data using the CIP protocol, potentially affecting system monitoring or operation. The specific nature of the error may be detailed in the CIP Error Code field.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Inspect EtherNet/IP network cabling between the Omron driver and the external device for damage, proper termination, and secure connections.
- 2
Verify IP address, subnet mask, and gateway settings on both the Omron EtherNet/IP driver and the external device for correct configuration and network compatibility.
- 3
Access the Omron EtherNet/IP driver's diagnostics or external device logs to retrieve the detailed CIP Error Code and identify the specific communication issue.
- 4
Verify the CIP connection parameters within the Omron EtherNet/IP driver's configuration (e.g., connection path, instance IDs, data sizes) against the external device's specifications.