08180000 hex

External Encoder Data Restoration Error

Omron · NJ/NX-series Machine Automation Controller

¿Qué significa 08180000 hex ?

Initialization of internal position data was not processed correctly in Fully-closed Control Mode and Absolute Value Mode. This is similar to the internal encoder error but specific to external encoders used in fully-closed loop systems.

Causas comunes

  • There is insufficient power supply voltage for the external encoder.
  • Noise is entering on the external encoder line.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the external encoder's power supply voltage at the encoder terminals and controller input against manufacturer specifications.

  2. 2

    Inspect all external encoder cabling for physical damage, proper routing, secure connections, and correct shielding termination at both the encoder and controller ends.

  3. 3

    Check Omron Sysmac Studio for correct external encoder module configuration, associated axis parameters (e.g., resolution, scaling, data format), and fully-closed loop settings.

  4. 4

    Perform a controlled power cycle of the Omron NJ/NX controller and associated servo system to force a fresh re-initialization of all connected devices.

Ver todos los códigos en este manual (96)
Datos técnicos verificados. Última actualización: March 2026