Traduciendo...
100C0000 hex

Event Level Setting Error

Omron · NX-series CPU Unit

¿Qué significa 100C0000 hex ?

The event level setting file contains incorrect or corrupted data. This error is detected at power-on or during a Controller reset, resulting in a major fault that stops the user program and Controller operation.

Causas comunes

  • The Controller's power supply was interrupted or communications with Sysmac Studio were disconnected during a download of the event level settings.
  • The Controller's power supply was interrupted during a Clear All Memory operation.
  • Failure of the non-volatile memory within the CPU Unit.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Perform a Memory All Clear operation on the Controller and then re-transfer the event level setting file from Sysmac Studio.

  2. 2

    If the error persists after re-transferring the event level settings, replace the CPU Unit.

Ver todos los códigos en este manual (17)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas