100C0000 hex
Event Level Setting Error
Omron · NX-series CPU Unit
¿Qué significa 100C0000 hex ?
The event level setting file contains incorrect or corrupted data. This error is detected at power-on or during a Controller reset, resulting in a major fault that stops the user program and Controller operation.
Causas comunes
- The Controller's power supply was interrupted or communications with Sysmac Studio were disconnected during a download of the event level settings.
- The Controller's power supply was interrupted during a Clear All Memory operation.
- Failure of the non-volatile memory within the CPU Unit.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Perform a Memory All Clear operation on the Controller and then re-transfer the event level setting file from Sysmac Studio.
- 2
If the error persists after re-transferring the event level settings, replace the CPU Unit.