Traduciendo...
A395.11
Memory Corruption Detected
Omron · SYSMAC CJ2 CPU Unit
¿Qué significa A395.11 ?
This flag indicates that memory corruption has been detected within the PLC. When this flag goes ON, the 'Number of Power Interruptions' (A514) will be cleared. This suggests a significant issue with the integrity of the PLC's internal memory or stored data.
Causas comunes
- Internal memory read/write errors within the CPU Unit.
- Corrupted program or parameter data due to unexpected events.
- Hardware malfunction affecting the CPU's memory modules.
- Unstable power supply leading to transient memory corruption.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Perform a memory check using the CX-Programmer to diagnose the extent of the corruption.
- 2
Upload the existing program and parameters from the PLC, then download a known good backup to restore data integrity.
- 3
Verify the PLC's power supply stability, checking for voltage sags, transients, or complete interruptions.
- 4
If the issue persists after reloading software and verifying power, replace the CPU Unit.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Omron SYSMAC CJ2 CPU Unit