Traduciendo...
A402.06
Special I/O Unit Data Exchange Error
Omron · SYSMAC CJ2 CPU Unit
¿Qué significa A402.06 ?
This fault indicates an error during data exchange between the CPU Unit and a Special I/O Unit. When this error occurs, the Special I/O Unit Error Flag (A402.06) is turned ON. The corresponding bit for the unit number (0-95) in A418 to A423 will also be set. The CPU Unit will continue operating, and the ERR/ALM indicator on the front of the CPU Unit will flash.
Causas comunes
- Communication failure during data exchange with a Special I/O Unit (unit numbers 0-95).
- Physical connection issue with the Special I/O Unit.
- Faulty Special I/O Unit.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Identify the faulty Special I/O Unit by checking the status of bits A418.00 to A423.15.
- 2
Inspect the physical connection and bus cables of the identified Special I/O Unit.
- 3
Verify the power supply to the Special I/O Unit.
- 4
Clear the error flag (A402.06) once the error condition is resolved.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Omron SYSMAC CJ2 CPU Unit