SERIAL COMMUNICATION FAULT

Otis · DSD 412 DC Elevator Drive

¿Qué significa 117/118 ?

Fault 117 occurs if serial communication does not start within 20 seconds after drive reset or power up. Fault 118 occurs if a valid serial communication message is not received for more than 150 milliseconds.

Causas comunes

  • Host system is not connected or not sending valid messages.
  • Electrical grounding noise interference.
  • Serial communication is not being used, but parameter #110 is set to selection 3.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Ensure that the host is connected and sending valid messages.

  2. 2

    Look for and correct electrical grounding noise interference problems.

  3. 3

    If serial communication is not being used, verify that parameter #110 is NOT set to selection 3.