CFI2

Download Transfer Fault

Schindler · Altivar 212 Variable Frequency Drive

¿Qué significa CFI2 ?

This fault occurs when the Altivar 212 drive's configuration is invalid or inconsistent, typically after a configuration download via PC software. It can also indicate an unsuccessful transfer due to rating differences between the source and target drives (e.g., uploading an ATV212N4 configuration to an ATV212M3).

Causas comunes

  • Invalid or inconsistent configuration loaded into the drive.
  • Configuration transfer using PC software failed due to rating mismatches.
  • Detected fault during an interruption of download configuration transfer.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the previously loaded configuration for consistency and compatibility.

  2. 2

    Load a compatible configuration that matches the drive rating.

  3. 3

    Before performing a download with PC software, uncheck "Display communication error" in the Tool / Environnement option / Startup/Comm. settings.