Traduciendo...
SCF3

Direct Ground Short-Circuit (Hard Detection)

Schneider Electric · Altivar Machine ATV320 Variable Speed Drive

¿Qué significa SCF3 ?

A hard detection of a direct ground short-circuit. This indicates a severe fault where a motor phase or internal component is directly shorted to earth ground. This condition poses a significant safety hazard and can cause severe damage to the drive. This fault can be manually cleared if the 'Reset restricted fault configuration' (HrFC) parameter is set to 'Yes'.

Causas comunes

  • Motor phase wire directly shorted to the motor frame or earth ground due to insulation failure.
  • Internal wiring within the drive or motor starter shorted directly to chassis ground.
  • Significant water ingress or conductive foreign material bridging a phase conductor to ground.
  • Damaged motor cable insulation causing a direct short from a phase conductor to conduit or machine frame.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Disconnect all motor phases (U, V, W) from the drive output terminals.

  2. 2

    2. Use a megohmmeter to measure insulation resistance from each motor phase (U, V, W) to the motor frame ground (PE).

  3. 3

    3. Visually inspect the motor terminal box for moisture, debris, or damaged wire insulation.

  4. 4

    4. Inspect the entire length of the motor cable for insulation damage, pinch points, or water ingress.

  5. 5

    5. If the motor and cable test clear, power down and check for internal drive wiring shorting to its chassis.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schneider Electric Altivar Machine ATV320 Variable Speed Drive