11

Overtemperature in output stage

SEW Eurodrive · Drives

¿Qué significa 11 ?

The temperature within the inverter's output stage has exceeded its safe operating limit. This indicates potential overheating due to excessive load, high ambient temperatures, or insufficient cooling for the drive electronics.

Causas comunes

  • Excessive ambient temperature around the MOVIMOT drive
  • Sustained overload condition on the motor, leading to higher inverter losses
  • Blocked or insufficient cooling airflow to the drive's heat sinks

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the drive's cooling fan for proper operation, obstructions, and unusual noises.

  2. 2

    Clean the drive's heatsinks and ensure all ventilation openings are free of dust and debris.

  3. 3

    Measure the ambient temperature inside the control cabinet at the drive's location and compare it to the drive's specified maximum operating temperature.

  4. 4

    Verify the drive's programmed motor data and load-related parameters (e.g., nominal current, overload settings) against the actual motor specifications and application requirements.

  5. 5

    Measure the actual motor current during a typical operating cycle and compare it against the motor's rated current and the drive's nominal output current.