43

Communication timeout (RS485 cyclical)

SEW Eurodrive · Drives

¿Qué significa 43 ?

A communication timeout occurred during cyclical communication via RS485. This results in the drive decelerating and stopping along its set ramp, indicating a disruption in the continuous data exchange.

Causas comunes

  • Interrupted or faulty communication link between the RS485 master and the MOVIMOT® inverter.
  • Too many MOVIMOT® inverters (slaves) connected to the RS485 master for cyclical communication, causing the communication cycle to exceed the configured timeout interval (e.g., more than 8 drives for a 1-second timeout).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check and re-establish the communication link between the RS485 master and the MOVIMOT® inverter, verifying RS+ and RS- terminal connections.

  2. 2

    Check the number of slaves connected to the RS485 master. If the MOVIMOT® inverter's timeout is set to 1 s, ensure a maximum of 8 MOVIMOT® inverters (slaves) are connected for cyclical communication to prevent timeouts.

  3. 3

    Reduce the message cycle time or increase the timeout interval if allowed by the application and master settings.

Ver todos los códigos en este manual (39)
Datos técnicos verificados. Última actualización: March 2026