97
Copy error
SEW Eurodrive · Drives
¿Qué significa 97 ?
An error occurred during the transmission of a parameter set or during a copy process. This typically happens if the DBG keypad or PC is disconnected, or the 24 V supply voltage is interrupted while copying data.
Causas comunes
- DBG keypad or PC disconnected during the copy process
- 24 V supply voltage switched off during the copying process
- 24 V supply voltage switched on during the copying process
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Load the factory setting using the DBG keypad or MOVITOOLS® MotionStudio software
- 2
Load the complete data record from the previous MOVIMOT inverter using the DBG keypad or MOVITOOLS® MotionStudio software
- 3
Acknowledge and reset the error