78
IPOS Software Limit Switch Exceeded
SEW Eurodrive · MOVIDRIVE compact System (MCF/MCV/MCS4_A)
¿Qué significa 78 ?
No immediate drive response, but a fault is indicated, in IPOS operating mode if the programmed target position falls outside the travel range defined by software limit switches. This signifies a position command that attempts to move beyond the safety boundaries.
Causas comunes
- IPOS has commanded the motor beyond its configured software limits.
- IPOS target position is outside the allowed travel range.
- Software limit switch parameters (e.g., P2070, P2071) are set incorrectly.
- Error in IPOS path planning exceeding limits.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the IPOS user program for target position commands that exceed defined limits.
- 2
Verify the configured position of the software limit switches for correctness.