EC6:8

Parameter Channel Data Length Error

SEW Eurodrive · MOVIDRIVE compact System (MCF/MCV/MCS4_A)

¿Qué significa EC6:8 ?

This return code, structured as Error class 6 (Access Error) and Error code 8 (Type conflict), indicates that a write service during configuration via the parameter channel specified a data length other than the expected 4 data bytes. This causes a conflict in data type interpretation.

Causas comunes

  • Data corruption during transmission on the internal bus.
  • Issue with the data packet structure from a connected module.
  • Incorrect number of bytes received for a parameter update.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check bit 4 and bit 5 for the data length setting in the management byte of the parameter channel to ensure it specifies 4 data bytes.