F109-42
Plausibility fault incorrect acceleration
SEW Eurodrive · MOVIDRIVE MDX60B/61B Variable Speed Drive
¿Qué significa F109-42 ?
The current acceleration has exceeded the configured maximum acceleration limit. This indicates a discrepancy between actual motor dynamics and the set parameters, potentially due to incorrect configuration or mechanical issues.
Causas comunes
- Measured acceleration value exceeds plausible limits.
- Encoder velocity or position data indicates unrealistic acceleration.
- Incorrect configuration of acceleration monitoring parameters.
- Sensor malfunction causing erratic acceleration readings.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the configuration (encoder screen: max. set speed).
- 2
Analyze the speed/acceleration profile using the SCOPE function.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas