Traduciendo...
F109-44
Plausibility fault in encoder interface (A3401 = encoder 1 and A3402 = encoder 2)
SEW Eurodrive · MOVIDRIVE MDX60B/61B Variable Speed Drive
¿Qué significa F109-44 ?
The encoder interface (A3401 or A3402) does not match the configured data. This suggests a mismatch between the physical encoder type/connection and the drive's settings.
Causas comunes
- Encoder data stream indicates a deviation from expected patterns.
- Mismatch in position or velocity feedback from encoder 1 (A3401) or encoder 2 (A3402).
- Faulty encoder communication protocol interpretation.
- Environmental interference corrupting encoder signals.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check encoder type and configuration (SSI/incremental).
- 2
Check the encoder connection/wiring.
- 3
Check the polarity of the encoder data.
- 4
Check function of the encoder.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: SEW Eurodrive MOVIDRIVE MDX60B/61B Variable Speed Drive