F109-56
Plausibility fault in encoder interface (A3401 = encoder 1 and A3402 = encoder 2)
SEW Eurodrive · MOVIDRIVE MDX60B/61B Variable Speed Drive
¿Qué significa F109-56 ?
The encoder interface (A3401 or A3402) does not match the configured data. This suggests a mismatch between the physical encoder type/connection and the drive's settings.
Causas comunes
- Encoder data plausibility check failed for encoder 1 (A3401) or encoder 2 (A3402).
- Position or velocity feedback is inconsistent.
- Encoder resolution mismatch or incorrect setup.
- Mechanical issue causing inconsistent encoder output.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check encoder type and configuration (SSI/incremental).
- 2
Check the encoder connection/wiring.
- 3
Check the polarity of the encoder data.
- 4
Check function of the encoder.