91

System error (MQ.. station addressability)

SEW Eurodrive · MOVIMOT Field Distributor

¿Qué significa 91 ?

One or more MOVIMOT stations could not be addressed by the MQ.. unit within the configured timeout interval. This indicates a system-level communication issue where stations are not responding or are incorrectly configured.

Causas comunes

  • One or more MOVIMOT stations could not be addressed by the MQ.. unit within the timeout period.
  • Problems with the voltage supply to the MOVIMOT stations or issues with the RS-485 cabling.
  • Incorrect or duplicate addresses configured for the MOVIMOT stations.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the voltage supply to all MOVIMOT stations.

  2. 2

    Check the RS-485 cabling for continuity, shielding, and proper termination.

  3. 3

    Verify the configured addresses of all MOVIMOT stations for uniqueness and correctness.