Traduciendo...
07
DC link voltage too high
SEW Eurodrive · MOVIMOT MM..D With AC Motor DRS
¿Qué significa 07 ?
The DC link voltage has exceeded its permitted threshold. This condition often arises from regenerative braking if the ramp time is too short, issues with the braking resistor/coil, or an invalid supply input voltage.
Causas comunes
- Ramp time set too short, leading to excessive regenerative energy
- Faulty connection between brake coil and braking resistor
- Incorrect internal resistance of brake coil or braking resistor
- Thermal overload in the braking resistor due to incorrect sizing for the application
- Invalid supply input voltage range
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Increase the ramp time setting
- 2
Check the connection between the braking resistor and brake coil and correct if necessary
- 3
Check the internal resistance of the brake coil and braking resistor (refer to 'Technical Data' section)
- 4
Check the supply input voltage for valid voltage range
- 5
Reset the error by switching off the DC 24 V supply voltage
- 6
Reset the error via the control system or dedicated reset function
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: SEW Eurodrive MOVIMOT MM..D With AC Motor DRS