Traduciendo...
F34

Ramp timeout

SEW Eurodrive · MOVITRAC 07B System

¿Qué significa F34 ?

The drive has failed to reach the start/stop speed within the specified ramp time. This fault can occur during a controlled stop if the stop ramp time t13 is exceeded, or if the set stop ramp (P136 / P146) is too short. It causes an immediate switch-off with inhibit.

Causas comunes

  • Ramp time (start or stop) set too short for the load inertia or application dynamics
  • Drive exceeded stop ramp time t13 after inhibit removal
  • Parameter P136 or P146 (stop ramp time) configured to an insufficient duration

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Extend the start or stop ramp time (e.g., P136 / P146 for stop ramp).

  2. 2

    Review the application's acceleration and deceleration requirements and adjust ramp times accordingly.

Ver todos los códigos en este manual (41)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: SEW Eurodrive MOVITRAC 07B System