A00541

Motor Data Identification Active

Siemens · SINAMICS G120

¿Qué significa A00541 ?

This alarm indicates that the motor data identification process (parameter P1910) is active or has been selected to run. This is a normal operational state during commissioning or motor tuning, where the drive is learning the motor's electrical characteristics.

Causas comunes

  • Motor data identification (e.g., P1910) has been manually activated from the HMI, engineering tool, or a control command.
  • The drive was configured to perform automatic motor data identification upon power-up or a specific event (e.g., after parameter reset).
  • A new motor has been connected or motor parameters have been significantly changed (e.g., P0304-P0311), triggering the need for re-identification.
  • Internal drive diagnostics are running the identification routine to verify motor model or connections.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Allow the motor data identification process (P1910) to complete its sequence; this is a normal operational state.

  2. 2

    2. Verify that no external conditions (e.g., mechanical load on the motor, motor not completely de-coupled) are interfering with the identification process.

  3. 3

    3. Check the status of parameter r0002 (drive operating state) to confirm the identification routine is progressing as expected.

  4. 4

    4. If the process appears stuck, cancel the identification (e.g., P1910=0) and re-initiate it, ensuring all motor parameters (P0304-P0311) are accurately entered.

Ver todos los códigos en este manual (109)