A01698

Safety commis./reset act.

Siemens · SINAMICS G120

¿Qué significa A01698 ?

The safety reset or safety commissioning process is currently active, indicated by parameter p0010 = 95. This prevents normal drive operation until the safety procedure is properly concluded, ensuring that all safety configurations are finalized and verified for safe machine control.

Causas comunes

  • Parameter P0010 is actively set to 95 (Safety commissioning menu) by an operator or through software, requiring manual completion.
  • A safety-related change was made, and the drive automatically entered commissioning mode, waiting for acknowledgement (P0976).
  • Incomplete or interrupted safety commissioning sequence from a previous attempt, leaving the drive in an active state.
  • Drive was powered off during an active safety commissioning process, causing it to remain in this state on restart.
  • Software glitch causing the drive to falsely register an active commissioning state, even without recent changes.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Navigate to parameter P0010 and ensure it is not set to 95; if it is, complete the safety commissioning steps as per the drive manual or set it back to 0.

  2. 2

    2. Acknowledge any pending safety parameter changes by setting parameter P0976 (Safety acknowledge) to the required value (e.g., 1 or 2).

  3. 3

    3. Review the drive's safety manual for the specific procedure to correctly exit the 'Safety commissioning active' state.

  4. 4

    4. Save all parameters to non-volatile memory (e.g., P0971=1) after confirming the safety configuration and commissioning status.

  5. 5

    5. Power cycle the drive and check P0010 again to ensure the safety commissioning mode has been exited successfully.

Ver todos los códigos en este manual (109)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas