Drive attempted to do an automatic clone during startup.
Siemens · SINAMICS G120
¿Qué significa F00064 ?
The drive attempted to perform an automatic parameter clone during startup but failed because the `Clone00.bin` file was not found in the `/USER/SINAMICS/DATA` directory on the MMC. This prevents automatic configuration, requiring manual intervention to either provide the file or disable the cloning function.
Causas comunes
- The `Clone00.bin` file is missing from the `/USER/SINAMICS/DATA` directory on the MMC card.
- The MMC card is not correctly inserted or is faulty, preventing access to the file system during startup.
- The `Clone00.bin` file is corrupted or incomplete, making it unusable for the automatic cloning process.
- Drive parameters (e.g., P00004 for Master ID or P00003 for Cloning source) are incorrectly configured, leading to an auto-clone attempt without a valid source.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
1. Verify the presence and integrity of the `Clone00.bin` file in the `/USER/SINAMICS/DATA` directory on the drive's MMC using a file browser or STARTER/TIA Portal.
- 2
2. Power down the drive, then carefully re-insert the MMC card, ensuring it is seated correctly in the slot, and power up.
- 3
3. Transfer a known good `Clone00.bin` file to the MMC card's `/USER/SINAMICS/DATA` directory from a reliable backup source.
- 4
4. Check drive parameters P00004 (Master ID) and P00003 (Cloning source) for correct configuration related to automatic cloning functions.
- 5
5. Perform a manual cloning operation from a known good configuration file via STARTER or TIA Portal to ensure parameter consistency.