Component replaced, acknowledgment/data save necessary
Siemens · SINAMICS G120
¿Qué significa F01640 ?
The system has detected that a component has been replaced, requiring acknowledgment and data saving to integrate the new part and ensure consistent operation. Failure to perform these steps can prevent proper functionality and lead to an inconsistent safety state.
Causas comunes
- Control Unit, Power Module, or Sensor Module replaced without proper acknowledgment procedure.
- Firmware update initiated but not fully completed or acknowledged.
- Drive parameter backup restored to a different hardware component or after component replacement without acknowledgment.
- Safety parameters (e.g., P9700) require acknowledgment after a change or component replacement.
- Inconsistency detected between the firmware versions or hardware IDs of connected modules.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Access parameter P0009 and set it to 30 (Acknowledge component replacement) to clear the fault.
- 2
After acknowledgment, perform a parameter save (e.g., P0977 = 1) to permanently store the new configuration to non-volatile memory.
- 3
Verify the firmware version of the newly installed component matches other components or the required system version.
- 4
If safety functions are involved, check and acknowledge any safety-related parameters (e.g., P9700=1) after the component replacement.
- 5
Cycle power to the drive after performing acknowledgment and saving parameters to ensure all components re-initialize correctly.