Traduciendo...
61429

Measuring axis not in basic/intended position

Siemens · SINUMERIK 828D

¿Qué significa 61429 ?

A measuring axis (rotary axis 1 or 2) is not in its basic or intended position, particularly during the first measurement operation. The error code A specifically indicates that rotary axis 1 is not in its basic position. This fault prevents accurate measurements from being performed.

Causas comunes

  • The rotary measuring axis (e.g., C-axis on a turning machine) has not been homed or referenced to its zero position.
  • Encoder feedback for the measuring axis is lost or incorrect (e.g., cable damage, encoder fault, incorrect parameter P2043 for encoder type).
  • Mechanical slip or backlash in the rotary axis drive train, causing a discrepancy between commanded and actual position.
  • Machine data for the rotary axis home position or limits (e.g., MD34000 to MD34005) is incorrectly set.
  • External forces or collision preventing the axis from reaching its intended measuring position.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Manually jog the affected rotary measuring axis (e.g., C-axis) to its reference point and perform a homing/referencing procedure (e.g., G74 or specific machine function).

  2. 2

    2. Verify the integrity of the encoder cable for the measuring axis, checking for continuity and shielding effectiveness, and inspect the encoder feedback at the drive.

  3. 3

    3. Check the drive parameters for the rotary axis, specifically P2043 (Encoder type) and P2044 (Encoder resolution), ensuring they match the installed encoder.

  4. 4

    4. Observe the actual position feedback (r0030) of the rotary axis, comparing it to the commanded position, and check for any mechanical play or backlash.

  5. 5

    5. Review machine data related to the rotary axis's home position and software limits (e.g., MD34000, MD34001) for correct configuration.

Ver todos los códigos en este manual (37)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas