1501
Reconnection fault grid
SMA · SUNNY TRIPOWER X Solar Inverter
¿Qué significa 1501 ?
The inverter cannot connect to the utility grid. This occurs when the selected country standard or a set parameter value does not comply with the local grid requirements, preventing proper grid synchronization.
Causas comunes
- Incorrect country standard configuration in the inverter.
- Parameter values for grid connection settings do not match local utility grid requirements.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the configured country standard. Select the parameter Set country standard and check its value to ensure it is correct for the local grid.
Datos técnicos verificados. Última actualización: March 2026