77

Too Many Active Connections

Vacon · 100 FLOW Application Guide

¿Qué significa 77 ?

The drive has detected more than 5 active fieldbus or PC tool connections simultaneously. The system limits concurrent connections to a maximum of 5. Exceeding this limit can cause communication instability or prevent new connections.

Causas comunes

  • More than 5 simultaneous connections from PC tools (e.g., programming software, monitoring tools) to the drive's communication ports.
  • Multiple fieldbus masters or controllers attempting to establish concurrent connections with a single drive.
  • Network misconfiguration or a faulty fieldbus device causing persistent, phantom connections to remain active.
  • A PC tool or fieldbus master connection was not properly terminated, leaving an active session open in the drive's memory.
  • Drive firmware limitation or bug misinterpreting connection requests, leading to an inflated connection count.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Identify and disconnect all non-essential PC tools (e.g., commissioning software, diagnostic tools) from the drive's communication ports.

  2. 2

    2. Review the fieldbus network topology to ensure only one fieldbus master is configured to communicate with the drive.

  3. 3

    3. Power cycle the drive and any connected fieldbus masters or HMI panels to clear all active communication sessions.

  4. 4

    4. Use a network monitoring tool (if applicable) to identify the source of multiple connection attempts to the drive's IP address or node ID.

  5. 5

    5. Verify the drive's communication parameters (e.g., P4-00 for fieldbus type, P4-99 for communication diagnostics) for any errors or abnormal settings.

  6. 6

    6. Check if any remote access software or SCADA systems are maintaining persistent, unneeded connections to the drive.