13

Frequency converter under temperature

Vacon · 20 Compact

¿Qué significa 13 ?

The heat sink temperature of the frequency converter has fallen below -10 °C. This indicates that the ambient operating temperature is too low for the drive to function correctly or safely.

Causas comunes

  • Internal temperature of the frequency converter too low.
  • Ambient temperature below operating range.
  • Faulty temperature sensor (P1-30) in the converter.
  • Inadequate ventilation or blocked airflow.
  • Low load operation leading to reduced internal heating.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the ambient temperature in the vicinity of the frequency converter and ensure it is maintained above -10 °C.