14

Frequency converter overtemperature

Vacon · NX All-in-One Application

¿Qué significa 14 ?

The heatsink temperature of the power unit has exceeded safe operating limits, specifically over 90 °C (194 °F), or 77 °C (170.6 °F) for NX_6 and FR6 series. An alarm triggers when the temperature surpasses 85 °C (185 °F), or 72 °C (161.6 °F). This indicates inadequate cooling or excessive internal heat generation, which can lead to component damage.

Causas comunes

  • Internal temperature of the frequency converter exceeds its safe operating limit.
  • Insufficient cooling of the converter (e.g., blocked fan, high ambient temperature).
  • Overload condition causing excessive heat generation within the converter.
  • Faulty temperature sensor within the converter.
  • Overvoltage or undervoltage transients affecting internal components.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the operational status of all cooling fans within the drive and ensure unobstructed airflow through the heatsink cooling fins.

  2. 2

    Visually inspect the heatsink for any accumulation of dust, lint, or debris, and thoroughly clean if necessary to improve thermal dissipation.

  3. 3

    Measure the ambient air temperature directly surrounding the drive enclosure — ensure it remains within the drive's specified operating temperature range.

  4. 4

    Review the drive's switching frequency parameter settings — consider reducing it if it is set too high in relation to the ambient temperature and motor load.

Ver todos los códigos en este manual (42)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Vacon NX All-in-One Application