Follower fault
Vacon · NX All-in-One Application
¿Qué significa 74 ?
This fault code is generated when the drive is configured in a Master Follower function and one or more of the connected follower drives experience a fault condition. This drive reports the fault state of another drive in the system. The root cause lies within the specific follower drive that tripped to fault.
Causas comunes
- Loss of communication with the master drive in a Master Follower configuration.
- Follower drive not receiving encoder feedback from the master.
- Incorrect configuration of Master Follower parameters (e.g., P2-30, P2-31).
- Encoder signal integrity issues from the master drive.
- Drive operating outside the specified speed or position range for follower mode.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify communication link between master and follower drives.
- 2
Check encoder output signal (e.g., A/B pulses) from the master drive's encoder terminal.
- 3
Confirm parameter P2-30 (Master/Follower Mode) is set correctly on the follower drive.
- 4
Verify parameter P2-31 (Follower Type) matches the master drive's configuration.
- 5
Ensure the master drive is operational and its encoder is functioning correctly.