Brake Chopper Supervision Fault

Vacon · NX Liquid-Cooled Drive

¿Qué significa 12 ?

This fault indicates a problem with the brake chopper system. Possible causes include the absence of a brake resistor, a broken or open-circuited brake resistor, or a failure of the brake chopper circuitry itself.

Causas comunes

  • Brake chopper resistor disconnected or faulty.
  • Brake chopper output short-circuited.
  • DC bus voltage too high during braking, exceeding chopper limits (P0400).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that a brake resistor is correctly installed and connected to the drive terminals.

  2. 2

    Measure the resistance of the brake resistor to ensure it is not broken or open-circuited.

  3. 3

    Inspect the cabling between the drive and the brake resistor for any damage or loose connections.