4mA supervision
Vacon · NXP AFE-II Drive
¿Qué significa F50 ?
The current at an analog input has dropped below the 4mA supervision limit. This typically indicates a failure in the signal source, a broken control cable, or a loose connection within the current loop circuitry. This means the drive is not receiving expected sensor feedback.
Causas comunes
- Break or damage in the control cable (e.g., 4-20mA loop) connected to the drive's analog input terminal (e.g., AI1).
- Malfunction or failure of the external 4-20mA current loop signal source (e.g., pressure transmitter, flow meter).
- Loose or corroded connection at the drive's analog input terminal block (e.g., AI1+, AI1-) or at the sensor's output terminals.
- Incorrect scaling parameter (e.g., P2-10 for Analog Input 1 Min) set above the actual minimum current detected.
- Internal damage to the drive's analog input circuit or signal conditioning board.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the current directly at the analog input terminals (e.g., AI1, AGND) using a multimeter to confirm it is below 4mA.
- 2
Measure the output current directly from the signal source device to verify its operational integrity.
- 3
Perform a continuity test on the control cable between the signal source and the drive's analog input terminals (e.g., AI1) using an ohmmeter.
- 4
Tighten all terminal connections at the drive's analog input and at the signal source device.
- 5
Review parameter P2-10 (Analog Input 1 Min) and P2-11 (Analog Input 1 Max) to ensure they are correctly configured for the sensor's range.