F82

Aux Voltage

Vacon · NXP AFE-II Drive

¿Qué significa F82 ?

This fault is triggered by a digital input fault, signaling an issue with the auxiliary voltage supply. This suggests a problem with the external auxiliary power source or its monitoring.

Causas comunes

  • Loss of the external auxiliary control voltage (e.g., 24VDC, 120VAC) used to power control circuits, external relays, or sensors.
  • Failure of the auxiliary power supply (e.g., transformer, switch-mode power supply) causing its output voltage to drop or disappear.
  • Overload or short circuit on the auxiliary voltage distribution circuit, tripping a protective device (e.g., circuit breaker, fuse).
  • Malfunctioning voltage monitoring device (e.g., voltage relay) for the auxiliary voltage supply, incorrectly signaling a fault.
  • Broken or loose control wiring between the auxiliary voltage monitoring device and the drive's digital input (e.g., DI8, COM).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the auxiliary voltage supply at its source (e.g., 24VDC power supply output) to confirm correct voltage levels.

  2. 2

    Identify the specific digital input (e.g., DI8) configured for auxiliary voltage monitoring via parameters like P2-08.

  3. 3

    Measure the voltage across the identified digital input terminal (e.g., DI8 to COM) to confirm the state signaled by the monitoring device.

  4. 4

    Inspect any circuit breakers or fuses protecting the auxiliary voltage supply circuit for trips or blown conditions.

  5. 5

    Trace the control wiring from the auxiliary voltage monitoring device to the drive's digital input for breaks, shorts, or loose connections.

Ver todos los códigos en este manual (34)
Datos técnicos verificados. Última actualización: March 2026