Traduciendo...
30

Safe disable

Vacon · NXS NXP

¿Qué significa 30 ?

The 'Safe Disable' input on an OPTAF board has opened, activating a safety interlock that prevents drive operation. This feature is typically used to safely shut down or inhibit the start-up of the drive for maintenance or emergency situations. The drive will remain disabled until this safety condition is cleared.

Causas comunes

  • Activation of an external safety device (e.g., emergency stop button, safety light curtain, door interlock) connected to the OPTAF board's Safe Disable inputs (e.g., SD1, SD2).
  • Break in the wiring to the Safe Disable inputs (e.g., SD1, SD2) on the OPTAF board, causing an open circuit.
  • Internal fault or malfunction within the OPTAF board's safety monitoring circuit.
  • Incorrect parameter configuration related to Safe Disable inputs (e.g., P6-01 "STO function") or acknowledgment sequence.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the status of all external safety devices connected to the OPTAF board's Safe Disable inputs (e.g., SD1, SD2) and ensure they are in a safe (closed circuit) state.

  2. 2

    Measure voltage and continuity at the Safe Disable input terminals (e.g., SD1, SD2) on the OPTAF board to confirm the external circuit is properly closed.

  3. 3

    Inspect the wiring from external safety devices to the OPTAF board for breaks, loose connections, or short circuits.

  4. 4

    Attempt to acknowledge or reset the safety fault via the drive's control panel or software if an acknowledgment function is available (e.g., pressing "Reset" button).

  5. 5

    Review relevant safety parameters (e.g., P6-01 "STO function," P6-02 "STO acknowledgment") to ensure correct configuration for the safety system.

Ver todos los códigos en este manual (54)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas