34

CAN bus communication

Vacon · NXS NXP

¿Qué significa 34 ?

A message sent over the CAN bus was not acknowledged by another device on the network. This typically points to a communication issue, such as an incorrectly configured device, a disconnected bus, or a fault in the CAN network's physical layer. Loss of communication can prevent proper control and monitoring of the drive.

Causas comunes

  • Missing or incorrect termination resistors (e.g., 120 Ohm) at both ends of the CAN bus network.
  • Break or short circuit in the CAN bus cabling (CAN_H, CAN_L, CAN_GND) causing signal degradation or loss.
  • Incorrect CAN bus speed (baud rate) or node ID (address) configured on one or more devices (e.g., P3-10 "CAN baud rate", P3-11 "CAN node ID").
  • Power supply issue to one of the CAN bus devices, preventing it from communicating.
  • Defective CAN bus transceiver chip on one of the connected devices or the drive itself.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the presence and correct value (e.g., 120 Ohm) of termination resistors at both physical ends of the CAN bus network using an ohmmeter.

  2. 2

    Check continuity and shielding of the CAN bus cable (CAN_H, CAN_L, CAN_GND) for breaks, shorts, or loose connections at each device.

  3. 3

    Confirm that all devices on the CAN bus have unique node IDs (e.g., P3-11) and are configured for the identical baud rate (e.g., P3-10).

  4. 4

    Measure the voltage levels on CAN_H and CAN_L lines (relative to CAN_GND) using an oscilloscope to check signal integrity and common mode voltage.

  5. 5

    Temporarily disconnect devices one by one to isolate a potential faulty device or reconfigure the network with fewer devices to identify the source of the communication issue.

Ver todos los códigos en este manual (54)
Datos técnicos verificados. Última actualización: March 2026