Traduciendo...
59

Follower communication

Vacon · NXS NXP

¿Qué significa 59 ?

Communication has been lost between the Master and Follower drives via the SystemBus or CAN communication link. This could be due to incorrect option board parameters or a damaged/disconnected communication cable (optical fibre or CAN). Loss of communication prevents synchronized operation in a master-follower system, leading to operational halts.

Causas comunes

  • Physical disconnection or damage to the SystemBus/CAN communication cable between master and follower drives.
  • Incorrect termination resistors (e.g., 120 Ohm) on the CAN network, leading to signal reflection.
  • Faulty or incorrectly installed communication option board (e.g., MCB-103) in the master or follower drive.
  • Master drive communication parameters (e.g., P8-10, P8-11) or follower drive address (P8-01) mismatched.
  • EMI interference or ground loops affecting communication cable integrity.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect SystemBus/CAN communication cable for physical damage, proper seating, and correct pinout between master and follower units.

  2. 2

    Measure resistance across the CAN_H and CAN_L terminals at each end of the bus (should be approx. 60 Ohms if correctly terminated).

  3. 3

    Verify communication option board (e.g., MCB-103, MCA-101) is securely installed and recognized by the drive (check P8-XX status).

  4. 4

    Confirm master drive communication parameters (e.g., P8-10, P8-11 for baud rate) and follower addresses (P8-01) are identical across all connected drives.

  5. 5

    Check for proper shielding and grounding of the communication cable to mitigate electromagnetic interference.

  6. 6

    Swap communication cable with a known good one to rule out cable fault.

Ver todos los códigos en este manual (54)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas