Traduciendo...
BUS-LED 5-2
Maximum output data length exceeded (Fault code 5, argument 2)
Wago · Modular I/O System PROFIBUS DP
¿Qué significa BUS-LED 5-2 ?
The total length of output data configured for the Fieldbus Coupler surpasses the maximum allowed limit (128 bytes, or 244 bytes from SW 03 onwards). This suggests that too many output modules are connected or their output data structures are excessively large, exceeding the coupler's capacity.
Causas comunes
- The number of connected output modules exceeds the coupler's maximum data capacity
- Total configured output data length is greater than 128 bytes (or 244 bytes for SW 03+ firmware)
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Switch off the supply voltage of the coupler.
- 2
Remove some I/O modules from the node to reduce the total output data length.
- 3
Switch the supply voltage on again to restart the coupler.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Wago Modular I/O System PROFIBUS DP