I/O-LED 1-6

Changed I/O module configuration found after AUTORESET (Fault code 1, argument 6)

Wago · Modular I/O System PROFIBUS DP

¿Qué significa I/O-LED 1-6 ?

The Fieldbus Coupler detected a discrepancy between its configured I/O module arrangement and the physically connected modules immediately after an AUTORESET. This means the actual hardware setup of the I/O node does not match the software configuration stored in the coupler.

Causas comunes

  • Physical I/O module arrangement does not match the current software configuration
  • I/O modules were added, removed, or reordered without updating the coupler's configuration

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Adapt the configuration in the engineering software to precisely match the physically connected I/O module arrangement.

  2. 2

    Load the updated configuration onto the coupler.

  3. 3

    Cycle the supply voltage of the coupler (off then on again) to restart the device and apply the new configuration.

Ver todos los códigos en este manual (21)
Datos técnicos verificados. Última actualización: March 2026