Traduciendo...
Er - 12

Current Detection Circuit Fault

Yaskawa · E7 Drive

¿Qué significa Er - 12 ?

The current flow exceeded the motor rated current, the current detection value symbol was reversed, or there is an open-phase condition on any of the U/T1, V/T2, and W/T3 output terminals. This indicates a severe issue with the motor wiring or the drive's internal current detection, risking motor or drive damage.

Causas comunes

  • Open phase condition on one of the motor output terminals (U/T1, V/T2, W/T3) or within the motor winding, leading to severely unbalanced current detection.
  • Internal drive current sensor fault or current detection circuit malfunction (e.g., offset error, current signal reversal).
  • Severe motor overload condition causing actual current to exceed the drive's detection threshold for an extended period.
  • Drive output phase short-circuited to ground or between phases, leading to immediate, excessive current flow.
  • Incorrect motor rated current (P2-01) or drive rated current configured incorrectly after a control board or power section replacement.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Disconnect the motor from drive output terminals U/T1, V/T2, W/T3. Perform an insulation resistance test (megger) on each motor phase to ground and between phases.

  2. 2

    2. Verify all motor cable connections at the drive output terminals (U/T1, V/T2, W/T3) and motor terminal box are tight and free of corrosion.

  3. 3

    3. With motor disconnected, measure resistance between phases (U-V, V-W, W-U) at the drive output terminals; all values should be balanced within 5%.

  4. 4

    4. Verify motor rated current (P2-01) and motor overload protection (L3-01) parameters are correctly set according to motor nameplate data.

  5. 5

    5. If issue persists with the motor disconnected, perform a static test on the drive's output transistors (IGBTs) as per the manufacturer's service manual to check for internal current sensor or power circuit faults.