OPE01

kVA Selection Error

Yaskawa · E7 Drive

¿Qué significa OPE01 ?

An Operator Programming Error occurs when the Drive's kVA setting is incorrect, usually after a control board replacement. The Drive will not operate until this parameter is corrected.

Causas comunes

  • Control board replaced without correctly setting the kVA (or drive size) parameter for the specific power section, resulting in a mismatch.
  • Incorrect dip switch setting or internal jumper configuration on the control board for kVA selection, not matching the drive's physical rating.
  • Parameter (e.g., A1-02, or an internal diagnostic code) that defines the drive's kVA rating was manually misconfigured.
  • Firmware mismatch or corruption after a control board replacement leading to misinterpretation of kVA settings.
  • Control board incompatibility with the installed power section.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Consult the drive's hardware manual to locate the kVA selection method (e.g., dip switches, jumpers, or parameter A1-02) on the control board.

  2. 2

    2. Verify the physical kVA selection (switches/jumpers) on the control board matches the drive's nameplate kVA rating. Adjust as needed.

  3. 3

    3. If kVA is set via parameter (e.g., A1-02), ensure it is programmed to the correct value corresponding to the drive's power section rating.

  4. 4

    4. Power cycle the drive (turn off for 30 seconds, then on) after making any kVA selection corrections to allow the new setting to take effect.

  5. 5

    5. If issue persists, check the firmware version of the control board and ensure it is compatible with the power section of the drive.

Ver todos los códigos en este manual (64)