UV

Undervoltage Alarm

Yaskawa · E7 Drive

¿Qué significa UV ?

This is a warning displayed on the digital operator during a momentary power loss event. It indicates that incoming AC power has been interrupted, but the drive's control power supply is still being maintained. The alarm signifies the drive is in a ride-thru state and will precede a UV1 fault if power is not restored within the configured ride-thru time (L2-02).

Causas comunes

  • Momentary interruption or sag of the incoming AC power supply to the drive, lasting for a short duration.
  • Loss of one or more input phases for a very brief period due to grid instability or upstream protection.
  • Weak or unstable incoming AC power supply, making it susceptible to transient voltage dips.
  • Auxiliary control power supply (if external) experiencing a brief dip or interruption.
  • The drive's internal ride-through capability (e.g., L2-01 setting) is being utilized during a power event.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Monitor the incoming AC line voltage at R/L1, S/L2, T/L3 terminals with a power quality analyzer to detect voltage sags.

  2. 2

    2. Inspect upstream circuit breakers and fuses for signs of intermittent tripping or loose connections.

  3. 3

    3. Confirm all input power wiring connections at the drive are secure and free of corrosion.

  4. 4

    4. Verify the drive's ride-through settings (e.g., L2-01) are configured appropriately for the application's power stability.

  5. 5

    5. Consider installing a UPS (Uninterruptible Power Supply) for the control circuit or the entire drive if power quality is consistently poor.

Ver todos los códigos en este manual (64)
Datos técnicos verificados. Última actualización: March 2026