BUS Option Com Err

Option Communication Error

Yaskawa · F7 Drive

¿Qué significa BUS Option Com Err ?

After initial communication was established, the connection to the option board was lost. This indicates a broken connection or that the master controller stopped communicating, preventing data exchange.

Causas comunes

  • Loose or damaged ribbon cable connection between the drive's main board and the option board.
  • Faulty or misconfigured option board causing it to drop off the communication bus intermittently.
  • Master controller (e.g., PLC) stopping communication due to an internal fault or programming error, leading to bus timeouts.
  • Excessive electromagnetic interference (EMI) on the control wiring disrupting digital communication signals.
  • Incorrect communication protocol settings (e.g., baud rate in Parameter C6-01 or C6-02) between the drive and the option board.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Safely power down the drive, then visually inspect the option board's physical connection and ribbon cable for damage or looseness; reseat the board securely.

  2. 2

    Verify communication parameters (e.g., C6-01 for baud rate, C6-02 for data format) on the drive match the requirements of the option board.

  3. 3

    Measure the resistance across communication bus termination resistors (e.g., 120 Ohms for RS485) if the option board uses an external bus connection.

  4. 4

    Monitor communication activity using diagnostic tools (e.g., RX/TX LEDs on the option board or master) to pinpoint where data flow ceases.

  5. 5

    Temporarily swap the option board with a known good unit to isolate whether the fault is with the board or the drive's main control unit.