Traduciendo...
DIFF

Differential Feedback Detected

Yaskawa · iQpump1000

¿Qué significa DIFF ?

This fault (or minor fault/alarm) occurs when the difference between the PID Feedback and the Differential Feedback (monitor H3-OO = 28) exceeds the level set in parameter P4-18 for the duration specified in P4-19. It indicates an inconsistency in the feedback signals used for PID control.

Causas comunes

  • Malfunctioning or incorrect feedback transducer(s)
  • Parameter P4-18 (differential level) set too low for the application
  • Parameter P4-19 (differential time) set too short for the application

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Replace the PID feedback transducer or transducers if suspected of malfunction.

  2. 2

    Verify parameter P4-18 (Differential Level) setting to ensure it is appropriate for the system.

  3. 3

    Verify parameter P4-19 (Differential Time) setting to ensure it is appropriate for the system.

  4. 4

    Verify parameter P4-20 (Differential Hold) setting.

Ver todos los códigos en este manual (45)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas