Traduciendo...
FbH

PID Feedback Loss (High)

Yaskawa · iQpump1000

¿Qué significa FbH ?

The analog input programmed for PID feedback has risen above 21 mA. This occurs when the PI feedback source is incorrectly installed, not working, or has a wiring issue. The drive's response to this condition is controlled by parameters b5-12 and b5-13.

Causas comunes

  • PI feedback source is incorrectly installed or not working
  • Analog input programmed for PID feedback has risen above 21 mA
  • Wiring issue in the PID feedback circuit

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Confirm that the PID feedback source is installed and working properly

  2. 2

    Verify the analog input signal for PID feedback is within the expected 3-21 mA range

  3. 3

    Check drive parameters b5-12 (Feedback Loss 4 to 20 mA Detection Selection) and b5-13 (Feedback Loss Go To Frequency) for drive response settings

Ver todos los códigos en este manual (45)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas