Traduciendo...
FDBKL

PID Feedback Loss (Wire Break)

Yaskawa · iQpump1000

¿Qué significa FDBKL ?

The analog input programmed for PID feedback has risen above 21 mA or fallen below 3 mA, indicating a loss or out-of-range signal. This fault is effective only when b5-12 (Feedback Loss 4 to 20 mA Detection Selection) is set to 2 (fault).

Causas comunes

  • PID feedback source is not installed or not working properly.
  • Analog input signal for PID feedback has risen above 21 mA or fallen below 3 mA.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Confirm that the PID feedback source is installed and functioning correctly.

  2. 2

    Adjust drive response to this condition using b5-12 (Feedback Loss 4 to 20 mA Detection Selection) and b5-13 (Feedback Loss Go To Frequency).

  3. 3

    Control auto-restart of this fault using L5-42 (Feedback Loss Fault Retry Selection).

Ver todos los códigos en este manual (45)
Datos técnicos verificados. Última actualización: March 2026