FDBKL
PID Feedback Loss (Wire Break)
Yaskawa · iQpump1000
¿Qué significa FDBKL ?
The analog input programmed for PID feedback has risen above 21 mA or fallen below 3 mA, indicating a loss or out-of-range signal. This fault is effective only when b5-12 (Feedback Loss 4 to 20 mA Detection Selection) is set to 2 (fault).
Causas comunes
- PID feedback source is not installed or not working properly.
- Analog input signal for PID feedback has risen above 21 mA or fallen below 3 mA.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Confirm that the PID feedback source is installed and functioning correctly.
- 2
Adjust drive response to this condition using b5-12 (Feedback Loss 4 to 20 mA Detection Selection) and b5-13 (Feedback Loss Go To Frequency).
- 3
Control auto-restart of this fault using L5-42 (Feedback Loss Fault Retry Selection).