Traduciendo...
oH

Heatsink Overheat

Yaskawa · J1000

¿Qué significa oH ?

The temperature of the drive's heatsink has exceeded the pre-alarm level, typically set between 90-100 °C by parameter L8-02. This condition can be caused by high ambient temperatures, a malfunctioning internal cooling fan, or restricted airflow around the drive, leading to inadequate heat dissipation and potential damage to internal power components if ignored.

Causas comunes

  • Clogged or dirty heatsink cooling fins preventing effective heat dissipation.
  • Malfunctioning or failed heatsink cooling fan, leading to reduced airflow.
  • Ambient temperature exceeding the drive's specified operating range (e.g., above 50°C).
  • Excessive drive loading causing prolonged high current output, exceeding thermal capacity.
  • Incorrect mounting or insufficient clearance (e.g., less than 100mm top/bottom) around the drive.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the ambient temperature near the drive using a calibrated thermometer; ensure it is within specified limits.

  2. 2

    Inspect the heatsink cooling fins for dust, debris, or obstructions; clean thoroughly using compressed air.

  3. 3

    Verify the operation of the heatsink cooling fan; check if it spins freely and measure its current if possible.

  4. 4

    Check parameter L8-02 (Heatsink Overheat Level) and L8-03 (Heatsink Fan Control) for appropriate settings.

  5. 5

    Measure the output current (A) during peak load using a clamp meter; compare against drive/motor rated currents.

  6. 6

    Ensure adequate ventilation clearances around the drive as specified in the installation manual.

Ver todos los códigos en este manual (59)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas