Traduciendo...
UL3

Undertorque Detection 1

Yaskawa · P1000

¿Qué significa UL3 ?

The drive detected that the motor torque has fallen below a preset undertorque threshold. This can indicate a broken shaft, loss of load, or belt slippage, suggesting a mechanical failure.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the mechanical load and power transmission components (e.g., belts, couplings, gears, shafts) for signs of damage, wear, or slippage.

  2. 2

    Verify the undertorque detection threshold parameter (e.g., L8-0x) in the Yaskawa P1000 drive is set appropriately for the application's operating conditions.

  3. 3

    Verify the motor's nameplate data (e.g., Pn-002, Pn-003, Pn-004, Pn-005) is accurately programmed into the Yaskawa P1000 drive.

  4. 4

    Inspect the motor and motor cables for any visible damage, loose connections, or signs of overheating.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas