Traduciendo...
EF

Run Command Fault

Yaskawa · VS-616G5 Variable Speed Drive

¿Qué significa EF ?

This fault indicates an issue with the run command or a conflict in the command source (e.g., local/remote, digital input, serial). It prevents the inverter from starting or continuing operation. This can happen if the run command is unexpectedly lost, or if there's a discrepancy in how the inverter is commanded to run.

Causas comunes

  • Conflicting run commands from multiple sources (e.g., digital input and serial communication) due to P0-01 (Run Source Selection) parameter misconfiguration.
  • Digital input terminal (e.g., S1, S2) assigned for run command is not activated or has an open circuit.
  • External safety interlock or E-stop circuit connected to a digital input preventing run command.
  • Local/Remote mode switch on the inverter is in an unexpected position, overriding the intended run command source.
  • Serial communication (MODBUS, network) run command not being sent or sent incorrectly.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify parameter P0-01 (Run Source Selection) is set correctly for the intended run command source (e.g., 0 for Keypad, 1 for Digital Inputs, 2 for Serial).

  2. 2

    Measure voltage at the assigned digital input terminal (e.g., S1-SC) when a run command is expected (e.g., 24VDC for ON).

  3. 3

    Check the state of external safety interlocks or E-stop buttons connected to the inverter's control terminals.

  4. 4

    If using serial communication, confirm the run command bit (e.g., Bit 0 of register 0001h for MODBUS) is being written correctly.

  5. 5

    Cycle power to the inverter and re-attempt the run command from a single, verified source.

Ver todos los códigos en este manual (34)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Yaskawa VS-616G5 Variable Speed Drive