Transmission error: data inconsistent (CRC2 error)
ABB · AC500
Hva betyr 20 ?
A transmission error occurred, specifically indicating data inconsistency (CRC2 error) during PROFIsafe communication. This suggests corruption or incorrect data during transmission, which is critical for maintaining safety integrity.
Vanlige årsaker
- Electromagnetic interference (EMI) on the PROFIsafe communication line (e.g., Ethernet cable) causing data corruption during transmission.
- Faulty PROFIsafe cable (e.g., broken shielding, damaged conductors) between the safety PLC and the safety I/O device.
- Incorrect PROFIsafe parameters (e.g., F_CRC_Length) configured in either the safety PLC or the safety I/O device.
- Hardware defect in the PROFIsafe interface of the safety PLC or the connected safety I/O device.
- Network component malfunction (e.g., switch, coupler) causing data integrity issues for PROFIsafe frames.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Inspect the PROFIsafe communication cable for physical damage and ensure proper shielding termination at both ends.
- 2
Check for strong sources of EMI near the PROFIsafe communication lines (e.g., unshielded motor cables, welding equipment).
- 3
Verify the configured PROFIsafe parameters, especially F_CRC_Length and F_WD_Time, for consistency between all safety devices.
- 4
Power cycle both the safety PLC and the associated safety I/O device.
- 5
Perform a cable test (e.g., continuity, attenuation) on the PROFIsafe communication line if possible.
- 6
Swap the suspected faulty PROFIsafe device (PLC or I/O) with a known good unit for testing.